Downloads
Crafted from high-quality materials, our LS-CS-S secondary cable is built to withstand extreme weather conditions, including heavy rain, snow, and intense sunlight. Its robust construction guarantees longevity and resilience, making it the ideal choice for both temporary and permanent airport lighting installations. The secondary cable is designed to provide consistent power supply to runway lights, taxiway lights, and other essential lighting fixtures, ensuring that pilots and ground crews can operate safely and efficiently.
One of the standout features of our cable is its exceptional flexibility, allowing for easy installation and routing around various airport layouts. Whether you are upgrading existing lighting systems or installing new ones, our cable adapts seamlessly to your needs. Additionally, it is resistant to abrasion and chemical exposure, further enhancing its suitability for the demanding airport environment.
Safety is our top priority, and our secondary cable is manufactured to meet international standards for electrical performance and safety. With superior insulation and shielding, it minimizes the risk of electrical interference and ensures optimal performance of your airport lighting systems.
1. Rated voltage is 0.6/lkV.
2. Main enterprise standard: Q/3204815S176.
3. Rated operation temperature of conductor in XLPE insulated cable is 90°C.
4. Max. conductor temperature at short circuit shall not exceed 250°C.
5. The temperature at installation shall not be less than -15·c.
6. The allowed bending radius shall not be less than 10 times O.D. of cable.
|
Name |
Type |
Size(mm2) |
| Copper core XLPO insulated secondary cable
for airport lighting with rated voltage 0.6/lKV |
DJ-JDKR
|
1X2. 5、1X4、1X6 |
| Copper core XLPE insulated secondary cable
for airport lighting with rated voltage 0.6/lKV |
2X2. 5、2X4、2X6 |
|
Type |
Size (mm2) |
Nominal thickness of insulation(mm) |
Nominal thickness of sheath(mm) |
Calculated O.D. of cable (mm) |
Calculated weight of cable(kg/km) |
|
DJ-JDKR-0.6/1kV |
1X2.5 |
1.2 |
—— |
4.6 |
42.7 |
| 1X4 |
5.1 |
58.5 |
|||
| 1X6 |
5.7 |
79.8 |
|||
| 2X2.5 |
0.7 |
1.8 |
11 |
146 |
|
| 2X4 |
12 |
188 |
|||
| 2X6 |
13 |
242 |
|
No |
Test items |
Test condition |
Technical requirements |
|
|
1 |
Conductor D.C. resistance |
2.5mm² |
20℃ |
≤7.41Ω/km |
|
4mm² |
≤4.61Ω/km |
|||
|
6mm² |
≤3.08Ω/km |
|||
|
2 |
A.C. voltage test |
The single core cable is immersed in water at room temperature for 1 hour, 3.5KV test voltage is applied for 5min between conductor and water. 3.0KV A.C. voltage is applied between cores for 5min. |
No breakdown occurs to insulation |
|
|
3 |
4h A.C. voltage test |
The water immersion duration shallnot be less than 1h. 2.4KV A.C. voltage test is applied on sample for 4h. |
No breakdown occurs to insulat6ion. |
|
|
4 |
Other tests |
refer to Q/320481SS/176 |
||