Our LS-CS-P Primary cable is constructed with high-quality materials that are resistant to harsh environmental factors, including extreme temperatures, moisture, and UV exposure. This makes it the ideal choice for both indoor and outdoor applications, ensuring that your airfield lights remain operational regardless of the weather. The cable features a robust insulation layer that protects against abrasion and chemical exposure, extending its lifespan and reducing maintenance costs.
With a focus on safety, our primary cable is designed to minimize electrical interference, ensuring that your lighting systems function without disruption.
Installation is a breeze with our user-friendly design, which allows for quick and efficient setup. Whether you are upgrading existing lighting systems or installing new ones, our primary cable provides a seamless solution that meets industry standards and regulations.
In addition to its superior performance, our Primary Cable for airfield lights is backed by a comprehensive warranty, giving you peace of mind and confidence in your investment. Choose our primary cable for airfield lights and experience the perfect blend of quality, reliability, and safety. Illuminate your airfield with confidence and ensure that every landing and takeoff is as safe as possible. Upgrade your lighting systems today and see the difference!
1.Rated voltage is 5KV.
2.Main executive standard: MH/T 6049-2008 Underground electrical cable for airport lighting circuits
3.Long-term allowed operation temperature of cable is 90°C.
4.Short circuit temperature of cable shall not be more than 250°C, duration shall not be more than 55
5.Temperature at installation shall not be less than -15°C.
6.The allowed bending radius of cable shall not be less than 12 times O.D. of cable.
|
Name |
Type |
Size(mm2) |
|
XLPE insulated PE sheathed underground electrical cable for airport lighting circuits |
DYJY |
1×6 |
|
XLPE insulated PVC sheathed underground electrical cable for airport lighting circuits |
DYJV |
|
Type |
Size(mm2) |
Nominal thickness of insulation(mm) |
Nominal thickness of sheath(mm) |
Calculated O.D of cable(mm) |
Calculated weight of cable(kg/km) |
|
DYJY-5kV |
6 |
2.8 |
1.8 |
14.6 |
266 |
|
DYJV-5kV |
300 |
|
No. |
Test items |
Test condition |
Technical requirements |
|
1 |
Conductor D.C resistance |
20°C |
≤3.08Ω/km |
|
2 |
Partial discharge test |
Test voltage 18KV |
(routine test) discharge magnitude shall not exceed 10pC (type test) discharge magnitude shall not exceed 5pC |
|
3 |
A.C. Voltage test |
18KV power frequency voltage for 5min. |
No breakdown occurs to insulation. |
|
4 |
4H A.C high voltage test |
A.C voltage 20KV applied for 4h |
No breakdown occurs to insulation. |
|
5 |
Other tests |
MH/T 6049-2008 refer to MH/T 6049-2008 |
|